Specification Rating input voltage 2000 VA / 1200 W Rating input frequency 60/50Hz (auto sensing) Input phase Single phase Input socket With Fuse Cold Start (0 to 100% load) Press the ON/OFF Switch Input Range (220V) 140-300 Rating output(VA) 2000 Rating output (W) 1200 Power factor 0.6 Rating output voltage (V) 220 Waveform Battery mode (simulated sine wave), AC mode(sine wave) AC Voltage Regulation ±10% (Battery mode) Rear output socket 4 x Universal – Battery backup Wavefo
Request a quote for pricing
Answered within one business day. Volume pricing available.
Nationwide delivery, installed in Lagos. Lead times Manufacturer warranty, claims handled by us. How it works Authorised reseller, SON certified. Quotes answered within one business day.
Overview
Specification
| Rating input voltage | 2000 VA / 1200 W |
| Rating input frequency | 60/50Hz (auto sensing) |
| Input phase | Single phase |
| Input socket | With Fuse |
| Cold Start (0 to 100% load) | Press the ON/OFF Switch |
| Input Range (220V) | 140-300 |
| Rating output(VA) | 2000 |
| Rating output (W) | 1200 |
| Power factor | 0.6 |
| Rating output voltage (V) | 220 |
| Waveform | Battery mode (simulated sine wave), AC mode(sine wave) |
| AC Voltage Regulation | ±10% (Battery mode) |
| Rear output socket | 4 x Universal – Battery backup |
| Waveform | Simulated Sine Wave (Battery mode) |
| Line Mode | Synchronize with the utility |
| Rating frequency | 60Hz or 50 Hz ± 1 Hz |
| Battery Mode | Yellow flashing |
| Short circuit protection Line Mode | Fuse & Firmware protection |
| Short circuit protection Battery Mode | Firmware Protection |
| Overload protection Line Mode | 110%±5%; Go to fault mode Line Mode after 5 minutes, 120%±5%; Go to fault mode immediately. |
| Overload protection Battery Mode | 110%±5%; Shutdown after 5 seconds, 120%±5%, Shutdown immediately |
| Indicators AC mode | Green Lighting |
| Indicators Battery Mode | Yellow Flashing |
| Indicators Fault | Red Lighting |
| Alarm Battery Mode | Sounding every 10 Seconds |
| Alarm Low Battery | Sounding every Second |
| Alarm Overload | Sounding every 0.5 second |
| Alarm Fault | Continuously sounding |
| Full Protection | Overload, discharge, and Overcharge protection |
| Transfer Time | Typical 2-6ms, 10ms max. |
| Transfer Time | Typical 2-6ms, 10ms max. |
| Communication Interface | Optional RS232/RJ11 |
| Battery and runtime Rating | 2 X 12V/9AH |
| Recharge time – Typical | 6-8 hours recover to 90% capacity |
| Charge current | About 1A at normal mode. |
| Dimension, W X H X D (cm) | 22.5 X 12.5 X 39 |
| Net Weight (kgs) | 12.7KGS |
| Humidity | 0-90 % RH @ 0- 40°C (non-condensing) |
| Noise Level | Less than 45dB |
| Compatible with OS | Supports Windows® 2000/2003/XP/Vista/2008/7 |
| Communication interface | Elite 2000pro (N/A), Elite 2000ipro (USB/RJ11) |